VOLT{1|2|3}:TRIG
Sets the AC voltage of each phase that is applied when INIT/INIT:NAME TRAN and a software trigger are sent.
This command is valid in AC mode (OUTP:COUP AC).
Single-phase three-wire output or Three-phase output (PCR-LE optional): Sets the AC voltage of all phases at once.
Command
U phase
[SOURce:]VOLTage1[:LEVel]:TRIGgered[:AMPLitude] {<numeric>|MINimum|MAXimum}
[SOURce:]VOLTage1[:LEVel]:TRIGgered[:AMPLitude]? [{MINimum|MAXimum}]
V phase
[SOURce:]VOLTage2[:LEVel]:TRIGgered[:AMPLitude] {<numeric>|MINimum|MAXimum}
[SOURce:]VOLTage2[:LEVel]:TRIGgered[:AMPLitude]? [{MINimum|MAXimum}]
W phase (Three-phase output only)
[SOURce:]VOLTage3[:LEVel]:TRIGgered[:AMPLitude] {<numeric>|MINimum|MAXimum}
[SOURce:]VOLTage3[:LEVel]:TRIGgered[:AMPLitude]? [{MINimum|MAXimum}]
Parameter
Value | L range: 0 to 152.5 H range: 0 to 305.0 A SCPI error (-222, "Data out of range") occurs if outside the range. The default value is 0. |
Unit | V |
For the setting that is applied when *RST is sent, see this table
For the setting that is applied when *RST is sent, see this table
For the setting that is applied when *RST is sent, see this table
Response
Response
Returns the target value of U phase to which the AC voltage is to change using a trigger in NR3 format in response to VOLT1:TRIG?.
Returns the target value of V phase to which the AC voltage is to change using a trigger in NR3 format in response to VOLT2:TRIG?.
Returns the target value of W phase to which the AC voltage is to change using a trigger in NR3 format in response to VOLT3:TRIG?.