AC Power Supply PCR-LE series

AC Power Supply PCR-LE2 series

AC Power Supply PCR-M series

Commnunication Interface Mannual


 

Tutorial

Visual Basic 2008

Communicate with the PCR-M/ PCR-LE/PCR-LE2 series using VISA through GPIB, RS232C, USB, or LAN.Visual Basic 2008.

Setting the "Project"

First, set the communication driver (VISA library) for the "Project."

Click "Project" on the menu bar, then select "Add Reference" to refer to "VISA COM 3.0 Type Library."

 

Communication through GPIB, RS232C, USB, or LAN

After setting the communication driver, you can communicate with the PCR through GPIB, RS232C, USB, or LAN.

The following describes the communication procedure using VISA.

Open the VISA

To communicate with an GPIB, RS232C, USB, or LAN device using VISA, you have to first open VISA. When you open VISA, specify the I/O resource.

Example : To open VISA by using USB

Set rm = CreateObject("VISA.GlobalRM")

Set msg = rm.Open("USB::0x0B3E::0x1024::00000001::INSTR", NO_LOCK, 0, "")

"USB::0x0B3E::0x1024::00000001::INSTR" is the I/O resource.

The I/O resource is specified by the following constructions. The part indicated with [ ] can be omitted. Enter the appropriate values in the parts specified in oblique characters.

GPIB GPIB[board]::PrimaryAddress[::SecondaryAddress][::INSTR]
Example: The primary address 3 of the measuring instrument connected to GPIB0.
GPIB0::3::INSTR
Serial
(RS232C)
ASRL[board][::INSTR]
Example : The measuring instrument connected to the serial port COM1.
   ASRL1::INSTR
USB USB[board]::VendorID::ProductID::SerialNumber[::InterfaceNumber][::INSTR]
Example: The USBTMC measuring instrument having vendor ID (VID) 2878, Product ID (PID) 4133 and serial number "00000001."
   USB0::0x0B3E::0x1024::00000001::INSTR
LAN*1 VXI-11 TCPIP[board]::hostname[::inst0][::INSTR]
Example :The measuring instrument whose IP address (hostname) is 169.254.7.8.
   TCPIP::169.254.7.8::INSTR
You can also set the LAN device name using the host name.
HiSLIP TCPIP[board]::hostname::hislip0[::INSTR]
Example :The measuring instrument whose IP address (hostname) is 169.254.7.8.
   TCPIP::169.254.7.8::hislip0::INSTR
You can also set the LAN device name using the host name.
SCPI-RAW TCPIP[board]::hostname::portno::SOCKET
Example :The measuring instrument whose IP address (hostname) is 169.254.7.8. (The "portno" setting of the PCR is normally 5025.)
   TCPIP::169.254.7.8::5025::SOCKET
You can also set the LAN device name using the host name.

*1: The hostname must be a valid mDNS hostname (a Bonjour hostname that ends in ".local") or a DNS hostname that is managed by an external DNS server (a full-qualified domain name—FQDN). If you are using an mDNS hostname, Apple Bonjour (alternatively, iTunes or Safari) must be installed on your PC.

For VISA, the alias can be used for the I/O resource.

When using the alias for the I/O resource, even if the alias name is hard-coded directly in the application, the alias name can be easily converted to the appropriate I/O resource name.

Example : When using the alias (MYDEV1) for the I/O resource.

Set msg = rm.Open("MYDEV1", NO_LOCK, 0, "")

When the alias is used, the actual I/O resource is specified by an external configuration table. When using USB (example for KI-VISA):

If you are using a VISA implementation other than KI-VISA, please refer to the applicable VISA manual.

Controlling the devices

Next, use "Read" and "Write" commands to control devices. You must include line-feed codes in the command character strings.

Example:

msg.WriteString ("VOLT 110" & vbLF)      'Set the AC voltage to 110 V

msg.WriteString ("FREQ 60" & vbLF)    'Set the frequency to 60.0 Hz 

msg.WriteString ("OUTP 1" & vbLF)              'Turn the output on

Closing the VISA

Close the VISA at the end.

You only need to include one "open" VISA command and one "close" VISA command in the program.

msg.Close

Sample program

Imports Ivi.Visa.Interop

 

Public Class Form1

 

   Dim rm As ResourceManager

   Dim msg As IMessage

 

   Private Sub Form1_Load(ByVal sender As System.Object, ByVal e As System.EventArgs) Handles MyBase.Load

      rm = CreateObject("VISA.GlobalRM")

      msg = rm.Open("GPIB0::1::INSTR", AccessMode.NO_LOCK, 0, "")     'Example: How to write GPIB

      'msg = rm.Open("MYDEV1", AccessMode.NO_LOCK, 0, "")  'Example: Using an alias

      'msg = rm.Open("USB0::0x0B3E::0x1024::00000001::INSTR", AccessMode.NO_LOCK, 0, "")  'Example: USB

      'msg = rm.Open("TCPIP::169.254.178.141::INSTR", AccessMode.NO_LOCK, 0, "")  'Example: LAN

      msg.TerminationCharacterEnabled = True

   End Sub

 

   'Query the instrument identity

   Private Sub cmdIdn_Click(ByVal sender As System.Object, ByVal e As System.EventArgs) Handles cmdIdn.Click

      msg.WriteString("*IDN?" & vbLF)

      TextBox1.Text = msg.ReadString(256)

   End Sub

 

   'Set the voltage and frequency

   Private Sub cmdCurr_Click(ByVal sender As System.Object, ByVal e As System.EventArgs) Handles cmdCurr.Click

      msg.WriteString("OUTP 0" & vbLF)

      msg.WriteString("VOLT 110" & vbLF)

      msg.WriteString("FREQ 60" & vbLF)

      msg.WriteString("OUTP 1" & vbLF)

   End Sub

 

   'Querys measurement DC voltage

   Private Sub cmdMeas_Click(ByVal sender As System.Object, ByVal e As System.EventArgs) Handles cmdMeas.Click

      msg.WriteString("MEAS:VOLT:DC?" & vbLF)

      TextBox1.Text = msg.ReadString(256)

   End Sub

 

   Private Sub Form1_Disposed(ByVal sender As Object, ByVal e As System.EventArgs) Handles Me.Disposed

      msg.Close()

   End Sub

 

END CLASS

>top

Command (function search)

Command (ABC search)

Command (Sub-system search)

Register

Appendix

Tutorial

AC power supply  PCR-M seriesAC Power Supply PCR-LE series
Communication Interface Manual

AC power supply  PCR-M seriesAC Power Supply PCR-LE2 series
Communication Interface Manual

AC power supply  PCR-M seriesAC Power Supply PCR-M series
Communication Interface Manual