PROG:EDIT:PHAS:RAMP
Sets the phase change of a sequence step.
Set the U phase angle with the U phase offset (PROG:EDIT:PHAS:UOFF).
Set the V phase angle with the U-V phase difference (PROG:EDIT:PHAS:UV).
Set the W phase angle with the U-W phase difference (PROG:EDIT:PHAS:UW).
This command is valid in single-phase three-wire output or three-phase output (PCR-LE optional).
Command
PROGram:EDIT:PHASe:RAMP <step_NR1>,<u-phase_char>[,<v-phase_char>[,<w-phase_char>]]
PROGram:EDIT:PHASe:RAMP? <step_NR1>
Parameter <step_NR1>
Value | 0~599 | Number of the step that you want to configure |
Parameter <u-phase_char>U phase change, <v-phase_char>V phase change, <w-phase_char>W phase change {OFF|LEAD|LAG}
Value | OFF | Ramp off |
LEAD | Ramp on, leading phase | |
LAG | Ramp on, lagging phase |
Response
Returns the phase change settings of the specified step in the following order in response to PROG:EDIT:PHAS:RAMP? <step_NR1>.
U phase change<char>, V phase change<char>, W phase change<char>