AC Power Supply PCR-LE series

AC Power Supply PCR-LE2 series

AC Power Supply PCR-M series

Commnunication Interface Mannual


 

PROG:EDIT:PHAS:UOFF

Sets the U phase offset of a sequence step.

This command is valid in single-phase three-wire output or three-phase output (PCR-LE optional).

Command

PROGram:EDIT:PHASe:UOFFset <step_NR1>,<enable_bool>,[<phase_numeric>]

PROGram:EDIT:PHASe:UOFFset? <step_NR1>

Parameter <step_NR1>

Value 0 to 599 Number of the step that you want to configure

Parameter <enable_bool> {ON|OFF|1|0}

Value ON(1) The U phase offset is set
OFF(0) The U phase offset is not set

Parameter <phase_numeric> {numeric|MAXimum|MINimum}

Value 0 to 359 U phase offset value
Unit DEG

Response

Returns the U phase offset value of the specified step in the following order in response to PROG:EDIT:PHAS:UOFF? <step_NR1>.

Whether the U phase offset is set or not set <NR1>, U phase offset value <NR3>