AC Power Supply PCR-LE series

AC Power Supply PCR-LE2 series

AC Power Supply PCR-M series

Commnunication Interface Mannual


 

MEAS{1|2|3}:CURR:AMPL:MAX:HOLD/ FETC{1|2|3}:CURR:AMPL:MAX:HOLD

MEAS{1|2|3}:CURR:AMPL:MAX:HOLD? starts a new measurement and then queries the peak current (the held value) of the specified phase.

FETC{1|2|3}:CURR:AMPL:MAX:HOLD? queries the peak current (the held value) of the specified phase without starting a new measurement.

This command is valid in single-phase three-wire output or three-phase output (PCR-LE optional).

You can use SENS:CURR:PEAK:CLE to clear the held peak value.

The valid modes (parameters to the OUTP:COUP command) are AC and DC.

Command

U phase

MEASure1[:SCALar]:CURRent:AMPLitude:MAXimum:HOLD?

FETCh1[:SCALar]:CURRent:AMPLitude:MAXimumv:HOLD?

V phase

MEASure2[:SCALar]:CURRent:AMPLitude:MAXimum:HOLD?

FETCh2[:SCALar]:CURRent:AMPLitude:MAXimumv:HOLD?

W phase (Three-phase output only)

MEASure3[:SCALar]:CURRent:AMPLitude:MAXimum:HOLD?

FETCh3[:SCALar]:CURRent:AMPLitude:MAXimumv:HOLD?

Response

Returns the peak current (the held value) of U phase in NR3 format in response to MEAS1:CURR:AMPL:MAX:HOLD? or FETC1:CURR:AMPL:MAX:HOLD?.

Returns the peak current (the held value) of V phase in NR3 format in response to MEAS2:CURR:AMPL:MAX:HOLD? or FETC2:CURR:AMPL:MAX:HOLD?.

Returns the peak current (the held value) of W phase in NR3 format in response to MEAS3:CURR:AMPL:MAX:HOLD? or FETC3:CURR:AMPL:MAX:HOLD?.

Unit: A

Command (function search)

Command (ABC search)

Command (Sub-system search)

Register

Appendix