SYST:CONF:EXT:SINP{1|2|3}:POL
Sets whether to output a signal whose polarity is the same as or opposite to that of the input signal.
This command is valid in amplifying the input waveform (optional).
Command
Single-phase
Single-phase three-wire output or Three-phase output (PCR-LE optional): Sets the signal source of all phases at once.
SYSTem:CONFigure:EXTernal:SINPut[0]:POLarity {NORMal|INVerted}
SYSTem:CONFigure:EXTernal:SINPut[0]:POLarity?
U-phase
SYSTem:CONFigure:EXTernal:SINPut1:POLarity {NORMal|INVerted}
SYSTem:CONFigure:EXTernal:SINPut1:POLarity?
U-phase
SYSTem:CONFigure:EXTernal:SINPut2:POLarity {NORMal|INVerted}
SYSTem:CONFigure:EXTernal:SINPut2:POLarity?
V-phase
SYSTem:CONFigure:EXTernal:SINPut3:POLarity {NORMal|INVerted}
SYSTem:CONFigure:EXTernal:SINPut3:POLarity?
Parameter
Value | NORMal | Output a signal whose polarity is the same as the input signal. |
INVerted | Output a signal whose polarity is opposite to that of the input signal. |
For the setting that is applied when *RST is sent, see this table
For the setting that is applied when *RST is sent, see this table
For the setting that is applied when *RST is sent, see this table
Response
Response
Single-phase
Returns the signal polarity in CHAR format in response to SYST:CONF:EXT:SINP:POL?.
Single-phase three-wire
Returns the U phase and V phase signal polarities separated by a comma in CHAR format in response to SYST:CONF:EXT:SINP:POL?.
Returns the U phase signal polarity in CHAR format in response to SYST:CONF:EXT:SINP1:POL?.
Returns the V phase signal polarity in CHAR format in response to SYST:CONF:EXT:SINP2:POL?.
Three-phase
Returns the U phase, V phase, and W phase signal polarities separated by a comma in CHAR format in response to SYST:CONF:EXT:SINP:POL?.
Returns the U phase signal polarity in CHAR format in response to SYST:CONF:EXT:SINP1:POL?.
Returns the V phase signal polarity in CHAR format in response to SYST:CONF:EXT:SINP2:POL?.
Returns the W phase signal polarity in CHAR format in response to SYST:CONF:EXT:SINP3:POL?.