AC power supply PCR-LE series
Specifications
Single-phase Three-wire output
Master-slave parallel operations
Communication interface (GPIB/ USB/ LAN)
Controlling the Output Using External Analog Signals
TYP: These are typical values. These values do not guarantee the performance of the PCR-LE Series.
Single-phase Three-wire output
The specifications are for comprehensive performance with the 2P05-PCR-LE installed in the PCR-LE Series to configure single-phase, three-wire system power supplies. Other specifications comply with those of the PCR-LE Series.
Phase difference of the output phase voltage*1 |
Resolution |
1° |
Accuracy |
Within ±(0.4°+5 µs) Within ±(0.4°+fo×1.8×10-3°), "fo" indicates the output frequency.*2 |
|
Range |
0° to 359° |
*1. Phase difference between output voltages (phase voltages) when each phase is checked from the neutral point.
In the condition in which no phase difference is varied (180° between phases),
Within 180°±(0.4°+5 µs), Within (180°±(0.4°+fo×1.8×10-3°))
*2. Examples of the results in which the noted expression was converted into an angle at a specific frequency
Within ±0.5° (for 60 Hz output)
Within ±1.2° (for 400 Hz output)
This specifications are for comprehensive performance with the 3P05-PCR-LE installed in the PCR-LE Series to configure three-phase system power supplies. Other specifications comply with those of the PCR-LE Series.
|
3P05-PCR-LE |
3P05-PCR-LE(500HZ LMT) |
|
Phase difference of the output phase voltage*1 |
Resolution |
1° |
|
Accuracy |
Within ±(0.4°+5 µs) Within ±(0.4°+fo×1.8×10-3°), "fo" indicates the output frequency.*2 |
||
Range |
0° to 359° |
||
AC mode output ratings (AC rms) Frequency |
1 Hz to 999.9 Hz |
1 Hz to 500.0 Hz |
*1. Phase difference between output voltages (phase voltages) when each phase is checked from the neutral point.
In the condition in which no phase difference is varied (120° between phases),
Within 120°±(0.4°+5 µs), Within (120°±(0.4°+fo×1.8×10-3°))
*2. Examples of the results in which the noted expression was converted into an angle at a specific frequency
Within ±0.5° (for 60 Hz output)
Within ±1.2° (for 4000 Hz output)
Master-slave parallel operations
The specifications given below cover the comprehensive performance of master-slave parallel operations in which the Parallel Operation Driver is installed in the PCR-LE AC power supplies. Other specifications comply with those of the PCR-LE Series AC power supplies.
Output voltage stability*1 |
Output current variation Changes in the 0 % to 100 % rating range |
±0.5 V |
Output frequency variation Changes in the rated range |
Within ±1.2 % |
|
Output voltage waveform distortion factor*1 |
0.5 % or less |
|
Output voltage response time |
60 µs(TYP)*2 |
|
Ammeter and power meter |
A total value for parallel operation is displayed.*3 |
|
Insulation resistance |
Input - enclosure Output - enclosure Input - Output |
500 Vdc [Insulation resistance of one PCR-LE power supply] / N N: Number of PCR-LE power supplies operated in parallel |
*1. Value obtained at the OUTPUT terminal board of the master power supply
For output voltage of 80 V to 150 V/160 V to 300 V and a load power factor of 1
*2. To change from output current of 0 A to the rated value and vice versa when the output voltage is 100 V/200 V and the load power factor is 1
*3. The resolution changes in accordance with the output capacity achieved during parallel operations. The accuracy is the same as that of the PCR-LE power supply.
Communication interface (GPIB/ USB/ LAN)
The specifications of the IB05-PCR-LE (GPIB), US05-PCR-LE (USB), and LN05-PCR-LE (LAN) interface boards are provided below.
GPIB |
Complies with IEEE Std 488.1-1987 SH1, AH1, T6, L4, SR1, RL1, PP0, DC1, DT1, C0, and E1 24-pin connector (receptacle) |
|
|
Message terminator |
LF or EOI during reception, LF + EOI during transmission |
Primary address |
1 to 30 |
|
USB |
Complies with the USB 2.0 specifications. Data rate: 12 Mbps (full speed), Socket B type |
|
|
Message terminator |
LF or EOM during reception, LF + EOM during transmission |
Device class |
Complies with the USBTMC-USB488 device class specifications |
|
LAN |
IEEE 802.3100Base-TX/10Base-T Ethernet Complies with the LXI Specification Ver.1.3 Class C, Data rate: 100 Mbps (Auto negotiation, full speed) NON AUTO MDIX IPv4, RJ-45 connector (Category 5; use a straight cable.) |
|
|
Communication protocol |
VXI-11/HiSLIP/SCPI-RAW |
Message terminator |
VXI-11, HiSLIP: LF or END during reception, LF + END during transmission SCPI-RAW: LF |
Controlling the Output Using External Analog Signals
The following specifications specify the comprehensive performance achieved when the Analog Interface is installed in the PCR-LE AC power supply. Other specifications not given here comply with those for the PCR-LE AC power supply.
|
EX05-PCR-LE |
EX06-PCR-LE |
|
Input terminal |
Maximum allowable input voltage |
±15 V |
|
Type |
BNC |
||
Input impedance |
10 kΩ ±10 % |
||
Isolation voltage |
±63 Vpeak |
||
Input voltage range |
0 V to 1.5 Vrms sine wave |
0 Vdc to +10 Vdc |
|
Input frequency range*1 |
1 Hz to 2k Hz (Sine wave) 1 Hz to 200 Hz (Rectangular wave) DC |
--- |
|
Frequency characteristics |
DC to 5k Hz: -3dB or less with respect to 200 Hz (On input of sine wave of 0.5 Vrms) |
--- |
|
Voltage amplification ratio (L, H range) |
100x, 200x (Outputs a 0 Vac to 150 Vac/0 Vac to 300 Vac with respect to an input of 0 Vac to 1.5 Vac) |
15x, 30x (Outputs a 0 Vac to 150 Vac/0 Vac to 300 Vac with respect to an input of 0 Vdc to 10 Vdc) |
|
Frequency setting range |
--- |
1 Hz to 999.9 Hz |
|
Output voltage distortion ratio*2 |
PCR-LE specifications + 0.5 % or less |
||
Output voltage temperature coefficient |
PCR-LE specifications + 200 ppm/°C(TYP) |
||
Insulation resistance
|
Between input (BNC) and chassi, input(BNC) and input, input (BNC) and output |
500 Vdc, 30 MΩ or more |
|
Withstand voltage |
Between input (BNC) and output, input (BNC) and output |
500 Vac for 1 minute |
|
Status signal output*3 |
OUTPUT ON STATUS |
Turns on when the output is on. |
|
ALARM STATUS |
Turns on when an alarm/trouble is detected. |
||
BUSY STATUS |
Turns on when the busy status. |
||
OOR STATUS |
Turns on when the current limit is exceeded and when overload occurs. |
||
External control*4 |
OUTPUT CONTROL*5 |
Output on with a low level signal/Output on with a high level signal. |
|
SEQ RUN*5 |
Run the sequence with a low level signal/Run the sequence with a high level signal. |
||
ALARM CLR*5 |
Alarm clear with a low level signal/Alarm clearwith a high level signal. |
||
SHUT DOWN*6 |
Output off with an open circuit/Output off with a short circuit |
*1. The measurable range of voltage, current, and power is DC and 1 Hz to 999.9 Hz
Set the frequency according to the input waveform period.
*2. When DC current is applied for EX06-PCR-LE or when a sine wave with distortion ratio of 0.1 % or less is applied for EX05-PCR-LE.
*3. Open collector outputs of photocouplers (30 Vdc, 8 mAmax.)
*4. Set the logic using CONFIG settings. The internal circuit is pulled up to 12 V through 1.3 kΩ.
*5. HIGH: Input terminal voltage of 11 V to 12 V or open; LOW: Input terminal voltage of 0 V to 1 V
*6. Open: Open or input terminal voltage of 11 V to 12 V; Short: Input terminal voltage of 0 V to 1 V
AC power supply PCR-LE series
Specifications