AC power supply PCR-LE series

Specifications


Main Unit Specifications

Unless specified otherwise, the specifications are for the following settings and conditions.

The warm-up time is 30 minutes (with current flowing).

TYP: These are typical values that are representative of situations where the PCR-LE Series operates in an environment with an ambient temperature of 23 °C (73.4 °F). These values do not guarantee the performance of the PCR-LE Series.

set: Indicates a setting.

reading: Indicates the readout value.

Input (AC rms)

AC mode output (AC rms)

DC mode output

AC + DC mode output

Output voltage stability

Output frequency stability, output voltage waveform distortion ratio, output voltage response speed, efficiency

Meters (fluorescent display)

Limit Values and Protection Functions

Power line abnormality simulations

Sequence operations

Special waveform output

Output impedance setting

Output on/off phase setting

Communication interface (RS232C)

Signal input/output

General

Rated output current characteristics (Derating)

Input (AC rms)

 

PCR500LE

PCR1000LE

PCR2000LE

PCR3000LE

PCR4000LE

PCR6000LE

PCR9000LE

Nominal input voltage

Single-phase two-wire input

100 Vac to 120 Vac, 200 Vac to 240 Vac*1

200 Vac to 240 Vac

---

Three-phase three-wire input

---

200 Vac to 240 Vac

Three-phase four-wire input

---

220 Vac to 240 Vac (phase voltage)

Input voltage range

Single-phase two-wire input

85 Vac to 132 Vac, 170 Vac to 250 Vac*1

170 Vac to 250 Vac

---

Three-phase three-wire input

---

170 Vac to 250 Vac

Three-phase four-wire input

---

187 Vac to 254 Vac (phase voltage)

Nominal input Frequency

50 Hz to 60 Hz

Input frequency range

47 Hz to 63 Hz

Apparent power

Approx.
0.93 kVA*2

Approx.
1.8 kVA*2

Approx.
3.6 kVA*2

Approx.
5.5 kVA*2

Approx.
7.3 kVA*2

Approx.
10.6 kVA*3

Approx.
15.7 kVA*3

Power factor

0.97 (TYP)*2

0.97 (TYP)*3

Max. current*4

Single-phase two-wire input

11.3 A, 5.5 A*1

22.0 A, 10.8 A*1

44.0 A, 21.5 A*1

66.0 A, 32.0 A*1

88.0 A, 43.0 A*1

64.0 A

---

Three-phase three-wire input

---

38 A

55.0 A

Three-phase four-wire input

---

21 A

30 A

*1. 100 V input type or 200 V input type

*2. When the input voltage is 100 V or 200 V, the output voltage is 100 V or 200 V, the output current is the rated value, the load power factor is 1, and the output frequency is between 40 Hz and 999.9 Hz.

*3. When the input voltage is 200 V, the output voltage is 100 V or 200 V, the output current is the rated value, the load power factor is 1, and the output frequency is between 40 Hz and 999.9 Hz.

*4. When the input voltage is 85 V (Single phase two-wire input 100 V input type), 170 V (Single phase two-wire input 200 V input type and Three-phase-three-wire input), 187 V (Three-phase Four-wire input).

TOP

AC mode output (AC rms)

 

PCR500LE

PCR1000LE

PCR2000LE

PCR3000LE

PCR4000LE

PCR6000LE

PCR9000LE

Voltage (output L range, output H range)

Rating

1 V to 150 V, 2 V to 300 V

Setting range

0 V to 152.5 V, 0 V to 305.0 V

Resolution

0.1 V

Accuracy*1

±(0.3 % of set + 0.6 V)

Max. current (output L range, output H range)*2

5 A, 2.5 A

10 A, 5 A

20 A, 10 A

30 A, 15 A

40 A, 20 A

60 A, 30 A

90 A, 45 A

Phase

Single-Phase

Power capacity

500 VA

1 kVA

2 kVA

3 kVA

4 kVA

6 kVA

9 kVA

Maximum peak current

Maximum current (rms) x 4 (TYP)*3

Maximum reverse current*4

30 % of the maximum current (rms)

Load power factor

0 to 1 (leading or lagging)*2

Frequency*2

Setting range

1 Hz to 999.9 Hz*5

Resolution

0.01 Hz (1.00 Hz to 100.0 Hz), 0.1 Hz (100.0 Hz to 999.9 Hz)

Accuracy

±1 × 10-4

*1. When the output frequency is between 45 Hz and 65 Hz, with no load, and at 23°C±5°C.

*2. When the maximum voltage is between 1 V and 100 V (L range) or 2 V and 200 V (H range) and the load power factor is between 0.8 and 1.
When the output voltage is between 100 V and 150 V (L range) or 200 V and 300 V (H range), the output current is reduced by the output voltage.
When the load power factor is between 0 and 0.8, the output current is reduced by the load power factor.
When the output frequency is between 1 Hz and 40 Hz, the output current is reduced by the output frequency.

*3. For capacitor-input rectifier loads, (at near the peak of the voltage waveform, excluding three-phase three-wire output).
The peak current that can be output decreases in accordance with the reduction in the absolute value of the instantaneous output voltage.
“Instantaneous output voltage versus instantaneous peak current ratio” (figs 5 and 6) for the representative voltage settings of each range is indicated in “Rated output current characteristics (Derating)”.

*4. When the output voltage is 100 V or 200 V and the output frequency is between 40 Hz and 999.9 Hz (current is -90 deg to -180 deg/ 90 deg to 180 deg out of phase with the output voltage).

*5. The frequency is limited to the range from 1 Hz to 500.0 Hz when the 3P05-PCR-LE(500HZ LMT) is installed in the PCR-LE series.

TOP

DC mode output

 

PCR500LE

PCR1000LE

PCR2000LE

PCR3000LE

PCR4000LE

PCR6000LE

PCR9000LE

Voltage (output L range, output H range)

Rating

-1.4 V to -212 V and +1.4 V to +212 V, -2.8 V to -424 V and -2.8 V to -424 V

Setting range

-215.5 V to +215.5 V, -431.0 V to +431.0 V

Resolution

0.1 V

accuracy*1

±(0.05 % of set + 0.05 V, 0.1 V)

Maximum current*2

3.5 A, 1.75 A

7 A, 3.5 A

14 A, 7 A

21 A, 10.5 A

28 A, 14 A

42 A, 21 A

63 A, 31.5 A

Maximum instantaneous current*3

Maximum current (rms) × 3.6

Power capacity

350 W

700 W

1.4 kW

2.1 kW

2.8 kW

4.2 kW

6.3 kW

*1. With no load at 23°C±5°C.

*2. When the output voltage is between 100 V and 212 V (L range), 200 V and 424 V (H range), the output current is reduced by the output voltage.

*3. Limited by the rated output current's rms value.

TOP

AC + DC mode output

 

Setting range

Resolution

Setting accuracy

Voltage setting

The AC voltage setting range is the same as the range in AC mode.

The DC voltage setting range is the same as the range in DC mode.

However, the peak AC+DC voltage must be within the DC voltage setting range.

AC voltage setting + DC voltage setting

Maximum current

The same as the setting in DC mode

Maximum instantaneous current

Power capacity

The same as the setting in DC mode

Frequency

The same as the setting in AC mode

TOP

Output voltage stability

 

PCR500LE

PCR1000LE

PCR2000LE

PCR3000LE

PCR4000LE

PCR6000LE

PCR9000LE

Line regulation*1

Within ±0.1 %

Load regulation (output L range, output H range)*2

Within ±0.1 V, within ±0.2 V

Output frequency variation*3

Response: FAST

Within ±0.2 %

---

Response: MEDIUM

Within ±0.3 %

Ripple noise in DC mode (5 Hz to 1 MHz components)

0.15 Vrms or less

0.2 Vrms or less

0.25 Vrms or less

Ambient temperature variation*4

±100 ppm/°C(TYP)

*1. With respect to changes in the rated range of input voltage.

*2. With respect to 0 % to 100 % changes in the ratingof output current.
When the output voltage is between 80 V and 150 V (L range) or 160 V and 300 V (H range) and the load power factor is 1. At the output terminal block. When the response mode is set to FAST or MEDIUM.

*3. Between 40 Hz and 999.9 Hz.
When the output voltage is between 80 V and 150 V (L range) or 160 V and 300 V (H range) and the load power factor is 1. This is the output line regulation with 200 Hz as the reference.

*4. With respect to changes in the operating temperature range.
When the output voltage range is 100 V or 200 V and the output current is 0 A.

TOP

Output frequency stability, output voltage waveform distortion ratio, output voltage response speed, efficiency

 

PCR500LE

PCR1000LE

PCR2000LE

PCR3000LE

PCR4000LE

PCR6000LE

PCR9000LE

Output frequency stability*1

Within ±5×10-5

Output voltage waveform distortion ratio*2

Response: FAST

0.2 % or less

---

Response: MEDIUM

0.3 % or less

Output voltage response speed*3

Response: FAST

20 µs(TYP)

---

Response: MEDIUM

30 µs(TYP)

Efficiency

54 % or more, 56 % or more*4

55 % or more, 57 % or more*4

58 % or more*5

*1. For changes within the rated ranges of all specifications

*2. When the output voltage is between 80 V and 150 V (L range) or 160 V and 300 V (H range) and the load power factor is 1.

*3. When the output voltage is 100 V or 200 V, the load power factor is 1, and the output current changes from 0 A to the rated value and from the rated value to 0 A.

*4. When the input voltage is 100 V or 200 V, the output voltage is 100 V or 200 V, the output current is the rated value, the load power factor is 1, and the output frequency is between 40 Hz and 999.9 Hz.

*5. When the input voltage is 200 V, the output voltage is 100 V or 200 V, the output current is the rated value, the load power factor is 1, and the output frequency is between 40 Hz and 999.9 Hz.

TOP

Meters (fluorescent display)

 

PCR500LE

PCR1000LE

PCR2000LE

PCR3000LE

PCR4000LE

PCR6000LE

PCR9000LE

Voltmeter*1

Resolution

0.1 V

Accuracy*2

±(1 % of reading +2 digits)

Ammeter*1

Resolution

0.01 A

0.1 A

Accuracy*3

±(1 % of reading +2 digits)

Wattmeter*4

Resolution

0.1 W, 1 W

1 W

Accuracy*5

±(1 % of reading +3 digits)

Frequencymeter*6

Resolution

0.01 Hz (1.00 Hz to 99.99 Hz), 0.1 Hz (100.0 Hz to 999.9 Hz)

*1. With the true rms display, a waveform with a crest factor of 3 or less, DC, output frequency between 40 Hz and 999.9 Hz, RMS, and AVE.

*2. 10 V to 424 V and at 23°C±5°C.

*3. 5 % of the max. rated current to max. rated current and at 23°C±5°C.

*4. When the output frequency is between 45 Hz and 65 Hz.

*5. 10 % to 100 % of the rated output capacity, when the load power factor is 1, and at room temperature.

*6. Displays the output frequency setting (frequency of the internal reference voltage).

TOP

Limit Values and Protection Functions

 

PCR500LE

PCR1000LE

PCR2000LE

PCR3000LE

PCR4000LE

PCR6000LE

PCR9000LE

Voltage

AC voltage upper limit

AC voltage lower limit

0.0 V to 305.0 V

DC voltage upper limit

DC voltage lower limit

-431.0 V to 431.0 V

Output overvoltage protection

AC/AC+DC mode

0.0 V to 474.1 V

Output overvoltage protection

DC mode

-474.1 V to 474.1 V

Output undervoltage protection

AC/AC+DC mode

0.0 V to 474.1 V

Output undervoltage protection

DC mode

-474.1 V to 474.1 V

Resolution

0.1 V

Frequency

Upper limit

Lower limit

1 Hz to 999.9 Hz*1

Resolution

0.01 Hz (1.00 Hz to 100.0 Hz), 0.1 Hz (100.0 Hz to 999.9 Hz)

Current

Current limit*2

AC mode

0.50 A to
5.50 A

1.00 A to
11.00 A

2.00 A to
22.00 A

3.00 A to
33.00 A

4.00 A to
44.00 A

6.00 A to
66.00 A

9.00 A to
99.00 A

Current limit*2

DC/AC+DC mode

0.35 A to
3.85 A

0.70 A to
7.70 A

1.40 A to
15.40 A

2.10 A to
23.10 A

2.80 A to
30.80 A

4.20 A to
46.20 A

6.30 A to
69.30 A

Positive peak current limit*3

0.50 A to
22.00 A

1.00 A to
44.00 A

2.00 A to
88.00 A

3.00 A to
132.0 A

4.00 A to
176.0 A

6.00 A to
264.0 A

9.00 A to
396.0 A

Negative peak current limit*3

-0.50 A to -22.00 A

-1.00 A to -44.00 A

-2.00 A to -88.00 A

-3.00 A to -132.0 A

-4.00 A to -176.0 A

-6.00 A to -264.0 A

-9.00 A to -396.0 A

Resolution*4

0.01 A (0.35 A to 100.0 A), 0.1 A (100.0 A to 396.0 A)

*1. The frequency is limited to the range from 1 Hz to 500.0 Hz when the 3P05-PCR-LE(500HZ LMT) is installed in the PCR-LE series. 

*2. The current that can actually be supplied is 1.1 times the rated current or the current limit, whichever is less.

*3. The current that can actually be supplied is the maximum peak current or the current limit, whichever is less.

*4. You can set the current in 0.01 A/ 0.1 A steps, but it may not change at this resolution depending on the relationship with the internal D/A resolution.

TOP

Power line abnormality simulations

 

Setting range

Resolution

Setting accuracy

T1

DEG

0 deg to 359 deg

1 deg

±1 deg

TIME

0.0 ms to 999.9 ms

0.1 ms

±(1×10-3+0.1 ms)

T2

0.0 ms to 99990 ms

0.1 ms

±(1×10-3+0.1 ms)

T3

0.1 ms to 9999.0 ms

0.1 ms

±(1×10-3+0.1 ms)

T4

0.0 ms to 99990 ms

0.1 ms

±(1×10-3+0.1 ms)

T5

0.0 ms to 99990 ms

0.1 ms

±(1×10-3+0.1 ms)

N

0 cycles to 999900 cycles

1 cycle

±1 cycle

T3 VOLT

The same as the output voltage setting range

LOOP

0 to 9998 repetitions or infinite repetitions

1 repetition

±1 repetition

TOP

Sequence operations

 

Setting range

Resolution

Setting accuracy

STEP

0 to 599

1

---

FREQ

The same as the output frequency setting range

ACV

The same as the output voltage setting range

TIME

0.1 ms to 1000 hour

0.1 ms

±(1×10-3+0.1 ms)

W.B. No.

The same as the special waveform output setting range

IMPEDANCE

The same as the output impedance setting range

DCV

The same as the output voltage setting range

S.PHASE

0 deg to 359 deg

1 deg

±1 deg

E.PHASE

0 deg to 359 deg

1 deg

±1 deg

TOP

Special waveform output

 

Setting range

Resolution

Setting accuracy

Waveform bank

0 to 63 (the waveform bank in 0 is read-only)

1

---

Crest factor

1.10 to 1.40

0.01

±0.01

TOP

Output impedance setting

 

Setting range

Resolution

Setting accuracy

PCR500LE

L range

0 Ω to 4.0 Ω

40 mΩ

±(10 % of set+80 mΩ)

H range

0 Ω to 16.0 Ω

160 mΩ

±(10 % of set+320 mΩ)

PCR1000LE

L range

0 Ω to 2.0 Ω

20 mΩ

±(10 % of set+40 mΩ)

H range

0 Ω to 8.0 Ω

80 mΩ

±(10 % of set+160 mΩ)

PCR2000LE

L range

0 Ω to 1.0 Ω

10 mΩ

±(10 % of set+20 mΩ)

H range

0 Ω to 4.0 Ω

40 mΩ

±(10 % of set+80 mΩ)

PCR3000LE

L range

0 Ω to 0.667 Ω

6.67 mΩ

±(10 % of set+13.33 mΩ)

H range

0 Ω to 2.667 Ω

26.67 mΩ

±(10 % of set+53.32 mΩ)

PCR4000LE

L range

0 Ω to 0.5 Ω

5 mΩ

±(10 % of set+10 mΩ)

H range

0 Ω to 2.0 Ω

20 mΩ

±(10 % of set+40 mΩ)

PCR6000LE

L range

0 Ω to 0.333 Ω

3.33 mΩ

±(10 % of set+6.67 mΩ)

H range

0 Ω to 1.333 Ω

13.33 mΩ

±(10 % of set+26.67 mΩ)

PCR9000LE

L range

0 Ω to 0.222 Ω

2.22 mΩ

±(10 % of set+4.44 mΩ)

H range

0 Ω to 0.889 Ω

8.89 mΩ

±(10 % of set+17.78 mΩ)

TOP

Output on/off phase setting

 

Setting range

Resolution

Setting accuracy

Phase setting

0 deg to 359 deg

1 deg

±1 deg

TOP

Communication interface (RS232C)

Software protocol

IEEE Std 488.2-1992

Command language

Complies with SCPI Specification 1999.0

RS232C

Complies with the EIA232D specifications

D-SUB 9-pin connector (male, Use a cross cable (null modem cable)),

 

Baud rate

9600 bps/ 19200 bps/ 38400 bps

Data length

8 bit / 7 bit

Stop bit

1 bit / 2 bit

Parity bit

Fixed to none

Flow control

OFF/ RTS・CTS

Message terminator

LF

TOP

Signal input/output

Trigger input

Pulse input for resuming the sequence function, BNC connector

Photocoupler input, drive voltage: 5 V, DC resistance: approx. 470 Ω, active with 7 mA source, pulse width: 10 µs

Trigger output

Pulse output at the start of sequence step execution, BNC connector

Open collector output, pulled up to +5 V with approx. 10 kΩ, DC resistance: 220 Ω, maximum sink current: 10 mA, pulse width: 10 µs

Status output

Output during periods T2, T3, and T4 in power line abnormality simulations and during a step output of the sequence function, BNC connector

Open collector output, pulled up to +5 V with approx. 10 kΩ, DC resistance: 220 Ω, maximum sink current: 10 mA

TOP

General

 

PCR500LE

PCR1000LE

PCR2000LE

PCR3000LE

PCR4000LE

PCR6000LE

PCR9000LE

Insulation resistance

Between input and chassis, output and chassis, and input and output

500 Vdc, 30 MΩ or more

500 Vdc, 10 MΩ or more

Withstand voltage

Between input and chassis, output and chassis, and input and output

1.5 kVac for 1 minute

Circuit method

Linear amplifier system

Withstand voltage

Operating
environment

Indoor use, overvoltage category II

Operating
temperature range

0 °C to +50 °C (32 °F to +122 °F)

Storage
temperature range

-10 °C to +60 °C (14 °F to 140 °F)

Operating humidity range

20 %rh to 80 %rh (no condensation)

Storage humidity range

90 %rh or less (no condensation)

Altitude

Up to 2000 m

Dimensions (chassis)

Up to 2000 m

Weight

Approx. 17 kg

(37.48 lb)

Approx. 35 kg

(77.16 lb)

Approx. 55 kg

(121.25 lb)

Approx. 82 kg

(180.78 lb)

Approx. 96 kg

(211.64 lb)

Approx. 140 kg

(308.65 lb)

Approx. 190 kg

(418.88 lb)

Input terminal

Single-phase two wire input

Inlet

M4

M5

M8

M8

M8

---

Three-phase three/four wire input

---

M5

Output terminal

M4

M4

M4

M5

M5

M8

M8

Accessories

Power cord

1 pc. With plug, Length: 3 m

---

Setup Guide

1 copy

Quick Reference

Japanese: 1 copy, English: 1 copy

Safety information

1 copy

CD-ROM

1 disc

Electromagnetic compatibility

(EMC) *1, *2

Complies with the requirements of the following directive and standards.

EMC Directive 2014/30/EU

EN 61326-1 (Class A *3 )

EN 55011 (Class A *3, Group 1 *4 )

EN 61000-3-2

EN 61000-3-3

The maximum length of all cables and wires connected to the PCR-LE Series must be less than 3 m.

Complies with the requirements of the following directive and standards.

EMC Directive 2014/30/EU

EN 61326-1 (Class A *3 )

EN 55011 (Class A *3, Group 1 *4 )

The maximum length of all cables and wires connected to the PCR-LE Series must be less than 3 m.

Safety*1

Complies with the requirements of the following directive and standard.

Low Voltage Directive 2014/35/EU *2

EN 61010-1

Class I *5 Pollution Degree2*6

*1. Does not apply to specially ordered or modified PCR-LEs.

*2. Only on models that have the CE marking on the panel.

*3. This is a Class A equipment. This product is intended for use in an industrial environment. This product may cause interference if used in residential areas. Such use must be avoided unless the user takes special measures to reduce electromagnetic emissions to prevent interference to the reception of radio and television broadcasts.

*4. This is a Group 1 equipment. This product does not generate and/or use intentionally radio-frequency energy, in the form of electromagnetic radiation, inductive and/or capacitive coupling, for the treatment of material or inspection/analysis purpose.

*5. This is a Class I equipment. Be sure to ground this product’s protective conductor terminal. The safety of this product is only guaranteed when the product is properly grounded.

*6. Pollution is addition of foreign matter (solid, liquid or gaseous) that may produce a reduction of dielectric strength or surface resistivity. Pollution Degree 2 assumes that only non-conductive pollution will occur except for an occasional temporary conductivity caused by condensation.

 

TOP

Rated output current characteristics (Derating)

The output voltage ratio is a percentage where 100 % represents an output voltage of 100 V (output L range) or 200 V (output H range) in AC mode or DC mode.

The output current ratio is a percentage where 100 % represents the maximum rated output current in AC mode or DC mode.

The instantaneous peak current ratio is the instantaneous peak current expressed as a percentage of the rated maximum output current.

The rated output current in AC mode depends on the output conditions (output voltage, load power factor, output frequency). The rated output current under given output conditions is the value obtained by converting the smaller of the two values: the product of the output current ratios derived from fig. 1 (output voltage) and fig. 3 (load power factor) and the output current ratio derived from fig. 4 (output frequency).

Fig.1 Output voltage ratio versus output current ratio (AC mode)

58125.jpg 

Fig.2 Output voltage ratio versus output current ratio (DC mode)

58133.jpg 

Fig.3 Load power factor versus output current ratio

58143.jpg 

Fig.4 Output frequency versus output current ratio

58151.jpg 

Fig.5 Instantaneous output voltage versus instantenous peak current ratio (AC mode L range, excluding three-phase three-wire output)

70432.jpg 

Fig.6 Instantaneous output voltage versus instantenous peak current ratio (AC mode H range, excluding three-phase three-wire output)

70445.jpg 

 

TOP

AC power supply PCR-LE seriesAC power supply PCR-LE series
Specifications