AC power supply PCR-LE series
Appendix
The following example shows how to set line voltage dips (short two phases: 70% residual voltage).
STEP |
0 |
1 |
2 |
3 |
ACVOLT [V] U phase AC voltage |
116.6 |
91.6 |
116.6 |
116.6 |
RAMP (ACVOLT) U phase voltage ramp |
OFF |
OFF |
ON |
OFF |
ACV V[V] V phase AC voltage |
116.6 |
116.6 |
116.6 |
116.6 |
RAMP (ACV V) V phase voltage ramp |
OFF |
OFF |
ON |
OFF |
ACV W [V] W phase AC voltage |
116.6 |
91.6 |
116.6 |
116.6 |
RAMP (ACV W) W phase voltage ramp |
OFF |
OFF |
ON |
OFF |
TIME [ms] Step time |
100 |
100 |
100 |
100 |
S.PHASE [deg] Starting phase angle |
FREE |
FREE |
FREE |
FREE |
E.PHASE [deg] Ending phase angle |
FREE |
FREE |
FREE |
FREE |
U PHA.OFFS [deg] U phase offset |
0 |
350 |
0 |
OFF |
RAMP (U PHA.OFFS) U phase ramp |
OFF |
OFF |
LAG |
OFF |
U-V PHAS [deg] U-V phase difference |
120 |
OFF |
OFF |
OFF |
RAMP (U-V PHAS) V phase ramp |
OFF |
-- |
-- |
--- |
U-W PHAS [deg] U-W phase difference |
240 |
250 |
240 |
OFF |
RAMP (U-W PHAS) W phase ramp |
OFF |
OFF |
LEAD |
--- |
PHAS. CNG sudden phase change |
OFF |
OFF |
OFF |
OFF |
In step 1, we will suddenly change phases, and in step 2, we will sweep phases. For sudden phase changes, we normally do not use the U phase offset, but because we will use both sudden phase change and phase sweep in this example, we will set the sudden phase change using the U phase offset.
In step 1, we set the U-W line voltage to 70%.
We set the U and W phase voltages to 91.6 V (ramp off), the U phase (U phase offset) to 350° (360° - 10°), and the W phase (U-W phase difference) to 250° (240° + 10°). Because these will be sudden changes, the U and W phase ramp settings are set to off.
In step 2, the U-W line voltage is varied from 70% to 100% over the duration of the step (1 second).
We set the U and W phase voltages to 116.6 V and the voltage ramp to on.
To sweep the U phase clockwise to 0°, we set the U phase (U phase offset) to 0° and set the ramp to LAG.
To sweep the W phase counterclockwise to 240°, we set the W phase (U-W phase difference) to 240° and set the ramp to LEAD.
AC power supply PCR-LE series
Appendix