Ragulated DC power supply  PAT-TM/TMX series

« PAT-T series product list

 

PAT80-100T (400 V input) specification

 

Unless specified otherwise, the specifications are for the following settings and conditions.

AC input

Nominal input rating   400 V, 50 Hz to 60 Hz, three-phase
Input voltage between U-G, V-G, and W-G *1 ±254 Vmax
Input voltage range 360 V to 440 V
Input frequency range 47 Hz to 63 Hz
Hold-up time for power interruption (MIN) 20 ms or greater (at 50 % load),
5 ms or greater (at the rated load)
Current (MAX) *2 18 A
Inrush current (MAX) *3 40 Apeak
Wattage (MAX) *2 10 kVA
Power factor (TYP) *4 0.95
Efficiency (MIN) *4 85 %

*1. At input terminals of the PAT.

*2. At the rated load.

*3. Excludes the charge current component that flows through the capacitor of the internal EMC filter circuit immediately after the POWER switch is turned on (within approximately 1 ms).

*4. Input voltage of 400 Vac, at the rated load.

Output

Rating Output power 8 kW
Output voltage 80.00 V
Output current 100.0 A
Voltage Preset range 0 % to 105 % of rtg *1
Setting accuracy ± (0.2 % of rtg +50 mV) *2
Line regulation ±(0.05 % of rtg + 5 mV) *3
Load regulation ±(0.1 % of rtg + 5 mV) *4
Transient response 5 ms *5
Ripple noise (p-p) 350 mV *6
(rms) 30 mV *7
Rise time (MAX) Rated load 100 ms *8
No load 100 ms *8
Fall time (MAX) Rated load 100 ms *9
No load 2000 ms *9
Temperature coefficient (MAX) 100 ppm/°C (during external control) *10
Current Preset range 0 % to 105 % of rtg *1
Setting accuracy ±(0.5 % of rtg + 50 mA) *2
Line regulation ±(0.1 % of rtg + 30 mA) *3
Load regulation ±(0.2 % of rtg +30 mA) *4
Ripple noise (rms) 300 mA *7
Temperature coefficient (TYP) 200 ppm/°C (during external control) *10

*1. The maximum preset voltage and current are used to determine constant voltage or constant current operation when the activation point of the constant voltage or constant current operation is set to the rated output voltage or current. It does not guarantee power supply to the load exceeding the rated output voltage or current.
To establish a constant voltage operation at the activation point (rated output voltage or current), set the output current (I Set) so that rated output current < I Set ≤ maximum preset current. Likewise, to establish constant current operation, set the output voltage (V Set) so that rate output voltage < V Set ≤ maximum preset voltage.

*2. The difference between the actual output voltage or output current and the preset value under constant voltage or constant current operation.

*3. Output voltage or output current fluctuation with respect to ±10 % fluctuation of the nominal input voltage under constant voltage or current operation.

*4. Output voltage or output current fluctuation when the output voltage or output current is set to the rated output voltage or current and the load is changed from rated load to no load under constant voltage or current operation.

*5. The time it takes for the output voltage fluctuation to recover from outside 0.1 % + 10 mV of the output voltage setting to within 0.1 % + 10 mV when the output current is changed from 100 % to 50 % or 50 % to 100 % of the rated output current under constant voltage operation. The output voltage when the output current is 100 % is used as a reference. When the remote sensing function is used.

*6. When the measurement frequency bandwidth is 10 Hz to 20 MHz.

*7. Output voltage is 10 % to 100 % of the rating when the measurement frequency bandwidth is 5 Hz to 1 MHz.

*8. The time it takes for the output voltage to rise from 10 % to 90 % of the rating when the output is turned on.

*9. The time it takes for the output voltage to fall from 90 % to 10 % of the rating when the output is turned off.

*10. When the ambient temperature is within the range of 0 °C to 50 °C.

Display function

Voltmeter Maximum display 99.99 (fixed decimal point)
Display accuracy ± (0.2 % of rdng +5 digits) at 23 °C ± 5 °C
Ammeter Maximum display 999.9 (fixed decimal point)
Display accuracy ± (0.5 % of rdng +5 digits) at 23 °C ± 5 °C
Operation display OUTPUT ON/OFF ON: OUTPUT LED illuminates (Green LED).
OFF: OUTPUT LED turns off.
ALM operation ALARM LED illuminates (Red LED). *1
CV operation CV LED illuminates (Green LED).
CC operation CC LED illuminates (Red LED).
RMT operation RMT LED illuminates during remote control (Green LED).
EXT operation EXT LED illuminates during external control (Green LED).
LOCK operation LOCK LED illuminates when the keys are locked (Green LED).

*1. Illuminates when the overvoltage protection (OVP), overcurrent protection (OCP), overheat protection (OHP), input open-phase protection (PHASE), fan failure protection (FAN), incorrect sensing connection protection (SENSE), overheat protection of the bleeder circuit (BOHP) and so on are activated.
Illuminates even when the breaker trips (even when the POWER switch is turned off). In this case, the LED illuminates for approximately 10 to 15 seconds.

Protection functions

Overvoltage protection (OVP) Turns off the output or trips the breaker (turns the POWER switch off).
ALARM LED illuminates.*1
  Selectable range 10 % to 111.5 % of the rated output voltage
Setting accuracy ± 2 % of rtg
Overcurrent protection (OCP) Turns off the output or trips the breaker (turns the POWER switch off).
ALARM LED illuminates.*1
  Selectable range 10 % to 111.5 % of the rated output current
Setting accuracy ± 3 % of rtg
Overheat protection (OHP) Trips the breaker (turns the POWER switch off). ALARM LED illuminates.
Input open-phase protection (PHASE) Turns the output off. ALARM LED illuminates.
Fan failure protection (FAN) Turns the output off. ALARM LED illuminates.
Incorrect sensing connection protection (SENSE) Turns the output off. ALARM LED illuminates.
Overheat protection of the bleeder circuit (BOHP) Turns the output off. ALARM LED illuminates.
Shut down (SD) Turns off the output or trips the breaker (turns the POWER switch off).
ALARM LED illuminates.*1

*1. Illuminates even when the breaker trips (even when the POWER switch is turned off). In this case, the LED illuminates for approximately 10 to 15 seconds.

Output signals

Monitor signal output*1 VMON (Voltage) At rated voltage output 10.00 V ± 0.25 V
At 0 V output 0.00 V ± 0.25 V
IMON (Current) At rated current output 10.00 V ± 0.25 V
At 0 A output 0.00 V ± 0.25 V
Status signal output *1, *2 OUTON STATUS Turns on when the output is on.
CV STATUS Turns on during CV operation.
CC STATUS Turns on during CC operation.
ALM STATUS Turns on when an alarm (OVP, OCP, OHP, BOHP, input open-phase protection, fan failure protection, incorrect sensing connection protection, or shutdown) is detected.
PWR OFF STATUS Stays on for approximately 10 to 15 seconds after the POWER switch turns off.
PWR ON STATUS Turns on when the POWER switch is on.

*1. J1 connector on the rear panel.

*2. Photocoupler open collector output, maximum voltage 30 V, maximum current (sink) 8 mA, insulated from the output and control circuits, and status signals are not mutually insulated.

Control functions

External control*1 EXT-V CV CONT *2 *3
(CV external voltage control)
0 % to 100 % of the rated output voltage in the range of 0 V to 10 V.
EXT-V (FAST) CV CONT *2 *3
(CV external voltage control FAST)
0 % to 100 % of the rated output voltage in the range of 0 V to 10 V.
EXT-R CV CONT *2
(CV external resistance control)
0 % to 100 % of the rated output voltage in the range of 0 kΩ to 10 kΩ.
EXT-R (FAIL SAFE) CV CONT *2
(CV external resistance control FAIL SAFE)
100 % to 0 % of the rated output voltage in the range of 0 kΩ to 10 kΩ.
EXT-V CC CONT *2 *3
(CC external voltage control)
0 % to 100 % of the rated output current in the range of 0 V to 10 V.
EXT-V (FAST) CC CONT *2 *3
(CC external voltage control FAST)
0 % to 100 % of the rated output current in the range of 0 V to 10 V.
EXT-R CC CONT *2
(CC external resistance control)
0 % to 100 % of the rated output current in the range of 0 kΩ to 10 kΩ.
EXT-R (FAIL SAFE) CC CONT *2
(CC external resistance control FAIL SAFE)
100 % to 0 % of the rated output current in the range of 0 kΩ to 10 kΩ.
OUTPUT ON/OFF CONT*4 Output on with a low TTL level signal/output on with a high TTL level signal.
SHUT DOWN*5 POWER switch off with a low TTL level signal.

*1. J1 connector on the rear panel.

*2. Set EXT-V, EXT-V (FAST), EXT-R, and EXT-R (FAIL SAFE) in the CONFIG settings. The selected function is enabled.

*3. The input impedance EXT-V CV CONT, EXT-V (FAST) CV CONT and EXT-V CC CONT, EXT-V (FAST) CC CONT is approximately 100 kΩ.
The setting accuracy is ±5 % of the rated output voltage or ±5 % of the maximum output current.

*4. Set the logic low/high using CONFIG settings.

*5. The output turns off even if the breaker trip setting of the CONFIG parameter is set so that the POWER switch does not turn off.

Interface

Common specifications Software protocol IEEE Std 488.2-1992
Command language Complies with the SCPI Specification 1999.0 specifications.
RS232C Hardware Complies with EIA232D.
D-SUB 9-pin connector (male) *1
Baud rate: 1200, 2400, 4800, 9600, 19200, and 38400 bps
Data length: 7 bits or 8 bits. Stop bit: 1 bit or 2 bits. No parity.
Flow control X-Flow or none.
Program message terminator LF during reception, CR/LF during transmission.
GPIB*2 Hardware Complies with IEEE Std 488.1-1987.
SH1, AH1, T6, L4, SR1, RL1, PP0, DC1, DT1, C0, and E1.
24 pin connector (receptacle)
Program message terminator LF or EOI during reception, LF+EOI during transmission.
Primary address 1 to 30
USB*2 Hardware Complies with USB 2.0. Data rate: 12 Mbps (full speed).
Socket B type
Program message terminator LF or EOM during reception, LF+EOM during transmission.
Device class Complies with the USBTMC-USB488 device class specifications.
LAN*2 Hardware IEEE 802.3 100Base-TX/10Base-T Ethernet
Complies with the LXI Class C, Specification 1.2.
IPv4, RJ-45 connector *3
Communications protocol VXI-11
Program message terminator LF or END during reception, LF+END during transmission.

*1. Use a cross cable (null modem cable).

*2. Factory option.

*3. Category 5, use a straight cable.

Other functions

General specifications

Weight Approx. 24 kg (52.91 lb)
Dimensions See the outline drawing
Environmental conditions Operating conditions Indoor use, Overvoltage Category II
Operating temperature 0 °C to +50 °C (32 °F to +122 °F)
Operating humidity 20 %rh to 85 %rh (no condensation)
Storage temperature -25 °C to +70 °C (-13 °F to +158 °F)
Storage humidity 90 %rh or less (no condensation)
Altitude Up to 2000 m
Cooling system Forced air cooling using a fan. (With fan control)
Grounding polarity Negative grounding or positive grounding possible.
Isolation voltage ± 250 Vmax
Withstand voltage Across the input terminals and chassis No abnormalities at 1500 Vac for 5 seconds.
Across the input terminals and the output terminals No abnormalities at 1500 Vac for 5 seconds.
Across the output terminals and chassis No abnormalities at 500 Vdc for 1 minute.
Insulation resistance Across the input terminals and chassis 500 Vdc, 30 MΩ or more. (at 70 %rh or less)
Across the input terminals and the output terminals 500 Vdc, 30 MΩ or more. (at 70 %rh or less)
Across the output terminals and chassis 500 Vdc, 30 MΩ or more. (at 70 %rh or less)
Safety Complies with the requirements of the following standard.
IEC61010-1:2001 (Class I *1, Pollution degree 2 *2)
Accessories Output terminal cover 2 sets (with screws)
Output terminal bolt set 2 sets (M10 × 20 mm bolts, nuts, and spring washers)
Heavy object warning label 1 pc.
J1/J2 connector kit 1 set (2 sets of protection covers, 2 sokets, and 30 pins)
Chassis connection wire 1 set (with screws)
Quick Reference (base model) 1 pc. (english), 1 pc. (japanese)
Setup Guide 1 copy
Safety Information 1 copy
CD-ROM 1 pc.

*1. This is a Class I sequipment. Be sure to ground the PAT-T series’s protective conductor terminal. The safety of this product is only guaranteed when the product is properly grounded.

*2. Pollution is addition of foreign matter (solid, liquid or gaseous) that may produce a reduction of dielectric strength or surface resistivity. Pollution Degree 2 assumes that only non-conductive pollution will occur except for an occasional temporary conductivity caused by condensation.

Dimensions

PAT-T Series Outline Drawing

Unit: mm (inch)

PAT-T Series Outline Drawing